    Unit: 
    Manufacturer: 
    Model Name: 
    Model Number: 
    Size:
    Airflow Measurement Station 
    Hydro-Air Engineering Services 
    Hydro-Air Flow Station 
    HAFS2424 
    24" X 24"
 

 

 

TEST # VP (in.wg.) Velocity  (fpm) Calculated CFM Referenced CFM Difference  (%) Pressure Drop (in.wg.)
1 0.5348 1981 8025.07 7923.27 1.28 0.0590
2 0.2952 1476 5962.26 5902.33 1.02 0.0350
3 0.1304 988 3962.71 3951.77 0.28 0.0140
4 0.0343 513 2032.36 2051.91 0.96 0.0030
5 0.0071 244 924.66 977.02 5.66 0.0005
 

 